1.83 BMS-IOM-Trend-DI

This page describes the device driver and the device window for a customized Building Management System (BMS) via Modbus. The BMS contains a variety of driver instances whereby this driver monitors a Digital Input and Temperature Collector Unit.

The driver uses the Modbus TCP protocol. The default TCP port used is 502.

As the driver is developed for a customized and unique system the online help does not contain any description of supported features and parameters.

Variables defined by this device driver

name type flags range
info.driver TEXT R/O StringRange R/O
lowLevel.cmd TEXT StringRange
lowLevel.reply TEXT R/O StringRange R/O
faults.99 ALARM R/O AlarmFlagRange R/O (Communication)
faults.commstat TEXT R/O StringRange R/O
info.type TEXT R/O StringRange R/O
info.port TEXT R/O StringRange R/O
info.frame TEXT R/O StringRange R/O
temperature.swRoom1 FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
temperature.itRoom FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
temperature.eqRoomA FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
temperature.eqRoomB FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
temperature.baRoom FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
temperature.outdoor FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
temperature.swRoom2 FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
oilTank.1 FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
oilTank.2 FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
config.minTempRoom FLOAT SAVE SETUP DoubleRange (0.0 .. 0.0)
config.maxTempRoom FLOAT SAVE SETUP DoubleRange (0.0 .. 0.0)
config.minTempOutdoor FLOAT SAVE SETUP DoubleRange (0.0 .. 0.0)
config.maxTempOutdoor FLOAT SAVE SETUP DoubleRange (0.0 .. 0.0)
config.minTankLevel FLOAT SAVE SETUP DoubleRange (0.0 .. 0.0)
faults.01 ALARM R/O AlarmFlagRange R/O (G59 Parallel Limit)
faults.02 ALARM R/O AlarmFlagRange R/O (Mains ACB)
faults.03 ALARM R/O AlarmFlagRange R/O (Generator ACB)
faults.04 ALARM R/O AlarmFlagRange R/O (Bus Coupler ACB)
faults.05 ALARM R/O AlarmFlagRange R/O (Bus Coupler ACB Trip)
faults.06 ALARM R/O AlarmFlagRange R/O (Harmonic Filter MCCB)
faults.07 ALARM R/O AlarmFlagRange R/O (Harmonic Filter MCCB Trip)
faults.08 ALARM R/O AlarmFlagRange R/O (Spare Supply 1 MCCB)
faults.09 ALARM R/O AlarmFlagRange R/O (Spare Supply 1 MCCB Trip)
faults.10 ALARM R/O AlarmFlagRange R/O (Spare Supply 2 MCCB)
faults.11 ALARM R/O AlarmFlagRange R/O (Spare Supply 2 MCCB Trip)
faults.12 ALARM R/O AlarmFlagRange R/O (Spare Supply 3 MCCB)
faults.13 ALARM R/O AlarmFlagRange R/O (Spare Supply 3 MCCB Trip)
faults.14 ALARM R/O AlarmFlagRange R/O (Spare Supply 4 MCCB)
faults.15 ALARM R/O AlarmFlagRange R/O (Spare Supply 5 MCCB)
faults.16 ALARM R/O AlarmFlagRange R/O (Spare Supply 6 MCCB)
faults.17 ALARM R/O AlarmFlagRange R/O (Spare Supply 7 MCCB)
faults.18 ALARM R/O AlarmFlagRange R/O (Pwr Build LP DB MCCB)
faults.19 ALARM R/O AlarmFlagRange R/O (Pwr Build LP DB MCCB Trip)
faults.20 ALARM R/O AlarmFlagRange R/O (Ext Light LP DB MCCB)
faults.21 ALARM R/O AlarmFlagRange R/O (Ext Light LP DB MCCB Trip)
faults.22 ALARM R/O AlarmFlagRange R/O (LV1A Surge Prot.Unit)
faults.23 ALARM R/O AlarmFlagRange R/O (PFC MCCB)
faults.24 ALARM R/O AlarmFlagRange R/O (PFC MCCB Trip)
faults.25 ALARM R/O AlarmFlagRange R/O (Maintenance LV1C Open)
faults.26 ALARM R/O AlarmFlagRange R/O (Maintenance LV1C Closed)
faults.27 ALARM R/O AlarmFlagRange R/O (Maintenance LV1C Trip)
faults.28 ALARM R/O AlarmFlagRange R/O (UPS1A 1 MCCB)
faults.29 ALARM R/O AlarmFlagRange R/O (UPS1A 1 MCCB Trip)
faults.30 ALARM R/O AlarmFlagRange R/O (UPS1A 2 MCCB)
faults.31 ALARM R/O AlarmFlagRange R/O (UPS1A 2 MCCB Trip)
faults.32 ALARM R/O AlarmFlagRange R/O (Eq. Bld. A LP DB MCCB)
faults.33 ALARM R/O AlarmFlagRange R/O (Eq. Bld. A LP DB MCCB Trip)
faults.34 ALARM R/O AlarmFlagRange R/O (Eq. Bld. B LP DB MCCB)
faults.35 ALARM R/O AlarmFlagRange R/O (Eq. Bld. B LP DB MCCB Trip)
faults.36 ALARM R/O AlarmFlagRange R/O (Spare Input 1)
faults.37 ALARM R/O AlarmFlagRange R/O (Spare Input 2)
faults.38 ALARM R/O AlarmFlagRange R/O (Spare Input 3)
faults.39 ALARM R/O AlarmFlagRange R/O (Spare Input 4)
faults.40 ALARM R/O AlarmFlagRange R/O (Spare Input 7)
faults.41 ALARM R/O AlarmFlagRange R/O (Spare Input 8)
faults.42 ALARM R/O AlarmFlagRange R/O (Spare Input 9)
faults.43 ALARM R/O AlarmFlagRange R/O (Spare Input 10)
faults.44 ALARM R/O AlarmFlagRange R/O (Spare Input 11)
faults.45 ALARM R/O AlarmFlagRange R/O (Spare Input 12)
faults.46 ALARM R/O AlarmFlagRange R/O (24VDC Battery Pack)
faults.47 ALARM R/O AlarmFlagRange R/O (Generator Inc ACB Open)
faults.48 ALARM R/O AlarmFlagRange R/O (Generator Inc ACB Closed)
faults.49 ALARM R/O AlarmFlagRange R/O (LV1A Supply ACB Open)
faults.50 ALARM R/O AlarmFlagRange R/O (LV1A Supply ACB Closed)
faults.51 ALARM R/O AlarmFlagRange R/O (LV1A Supply ACB Trip)
faults.52 ALARM R/O AlarmFlagRange R/O (Bus Coupler ACB Open)
faults.53 ALARM R/O AlarmFlagRange R/O (Bus Coupler ACB Closed)
faults.54 ALARM R/O AlarmFlagRange R/O (Main Incomer MCCB)
faults.55 ALARM R/O AlarmFlagRange R/O (LV1C Surge Protection)
faults.56 ALARM R/O AlarmFlagRange R/O (Maintenance LV1A Open)
faults.57 ALARM R/O AlarmFlagRange R/O (Maintenance LV1A Closed)
faults.58 ALARM R/O AlarmFlagRange R/O (Eq. Bld. A Surge Prot)
faults.59 ALARM R/O AlarmFlagRange R/O (Eq. Bld. B Surge Prot)
faults.60 ALARM R/O AlarmFlagRange R/O (Eq. Bld. A Prim.Surge Prot.)
faults.61 ALARM R/O AlarmFlagRange R/O (Eq. Bld. A Seco.Surge Prot.)
faults.62 ALARM R/O AlarmFlagRange R/O (Eq. Bld. B Prim.Surge Prot.)
faults.63 ALARM R/O AlarmFlagRange R/O (Eq. Bld. B Seco.Surge Prot.)
faults.64 ALARM R/O AlarmFlagRange R/O (IT Room AirCon)
faults.65 ALARM R/O AlarmFlagRange R/O (Switch Room 1 AirCon)
faults.66 ALARM R/O AlarmFlagRange R/O (Switch Room 2 AirCon)
faults.67 ALARM R/O AlarmFlagRange R/O (Battery Room Air Con)
faults.68 ALARM R/O AlarmFlagRange R/O (DB CP 1A MCCB Closed)
faults.69 ALARM R/O AlarmFlagRange R/O (DB CP 1A MCCB Tripped)
faults.70 ALARM R/O AlarmFlagRange R/O (Eq. Bld. A MCCB Closed)
faults.71 ALARM R/O AlarmFlagRange R/O (Eq. Bld. A MCCB Tripped)
faults.72 ALARM R/O AlarmFlagRange R/O (Eq. Bld. B MCCB Closed)
faults.73 ALARM R/O AlarmFlagRange R/O (Eq. Bld. B MCCB Tripped)
faults.74 ALARM R/O AlarmFlagRange R/O (Fire Alarm)
faults.75 ALARM R/O AlarmFlagRange R/O (Fire Alarm Panel)
faults.76 ALARM R/O AlarmFlagRange R/O (Ext Light ChangeOver Switch)
faults.77 ALARM R/O AlarmFlagRange R/O (PB Board Switch)
faults.78 ALARM R/O AlarmFlagRange R/O (BMS Panel C/O Switch)
faults.79 ALARM R/O AlarmFlagRange R/O (Key Signal LV1C)
faults.80 ALARM R/O AlarmFlagRange R/O (Key Signal UPS)
faults.81 ALARM R/O AlarmFlagRange R/O (Switch Room 1 Low)
faults.82 ALARM R/O AlarmFlagRange R/O (Switch Room 1 High)
faults.83 ALARM R/O AlarmFlagRange R/O (Switch Room 2 Low)
faults.84 ALARM R/O AlarmFlagRange R/O (Switch Room 2 High)
faults.85 ALARM R/O AlarmFlagRange R/O (IT Room Low)
faults.86 ALARM R/O AlarmFlagRange R/O (IT Room High)
faults.87 ALARM R/O AlarmFlagRange R/O (Equip. Bld. A Low)
faults.88 ALARM R/O AlarmFlagRange R/O (Equip. Bld. A High)
faults.89 ALARM R/O AlarmFlagRange R/O (Equip. Bld. B Low)
faults.90 ALARM R/O AlarmFlagRange R/O (Equip. Bld. B High)
faults.91 ALARM R/O AlarmFlagRange R/O (Battery Room Low)
faults.92 ALARM R/O AlarmFlagRange R/O (Battery Room High)
faults.93 ALARM R/O AlarmFlagRange R/O (Outdoor Low)
faults.94 ALARM R/O AlarmFlagRange R/O (Outdoor High)
faults.95 ALARM R/O AlarmFlagRange R/O (Level Tank 1 Low)
faults.96 ALARM R/O AlarmFlagRange R/O (Level Tank 2 Low)