1.159 Dantherm-ComboCooling1000

This page describes the monitoring only device driver and the device window for the Dantherm Combo Cooling 10000/1000 air conditioning controller device using Modbus protocol.

Device window pages

The following table shows which device window pages are available with this individual device type.

Configuration parameters

At the maintenance page of the device window there are a couple of configuration parameters which must be set to make the software talk to the device.

parameter description
address The device address (decimal) as set at the device's front panel.
Serial Remember to set the line parameters for the serial interface

The Dantherm unit is controlled through Modbus/TCP. The device IP address must be set as an interface name like with serial devices controlled through a network terminal adapter: "aaa.bbb.ccc.ddd:502" where 502 is the standard Modbus/TCP port number.

Variables defined by this device driver

name type flags range
info.driver TEXT R/O StringRange R/O
lowLevel.cmd TEXT StringRange
lowLevel.reply TEXT R/O StringRange R/O
faults.99 ALARM R/O AlarmFlagRange R/O (Communication)
faults.commstat TEXT R/O StringRange R/O
info.type TEXT R/O StringRange R/O
info.port TEXT R/O StringRange R/O
info.frame TEXT R/O StringRange R/O
info.version TEXT R/O StringRange R/O
info.product TEXT R/O StringRange R/O
fan.1.speed INTEGER R/O IntegerRange R/O (0 .. 0)
fan.2.speed INTEGER R/O IntegerRange R/O (0 .. 0)
fan.3.speed INTEGER R/O IntegerRange R/O (0 .. 0)
fan.1.drive INTEGER R/O IntegerRange R/O (0 .. 0)
fan.2.drive INTEGER R/O IntegerRange R/O (0 .. 0)
fan.3.drive INTEGER R/O IntegerRange R/O (0 .. 0)
room.temperature FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
ambient.temperature FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
supply.temperature FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
condensor.temperature FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
board.temperature FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
supply.voltage FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
system.state TEXT R/O StringRange R/O
fan.1.state TEXT R/O StringRange R/O
fan.2.state TEXT R/O StringRange R/O
fan.3.state TEXT R/O StringRange R/O
damper.1.state TEXT R/O StringRange R/O
damper.2.state TEXT R/O StringRange R/O
compr.state TEXT R/O StringRange R/O
ac.1.state TEXT R/O StringRange R/O
ac.2.state TEXT R/O StringRange R/O
heater.state TEXT R/O StringRange R/O
damper.1.position INTEGER R/O IntegerRange R/O (0 .. 0)
damper.2.position INTEGER R/O IntegerRange R/O (0 .. 0)
faults.01 ALARM R/O AlarmFlagRange R/O (Alarm 1)
faults.02 ALARM R/O AlarmFlagRange R/O (Alarm 2)
faults.03 ALARM R/O AlarmFlagRange R/O (Low voltage)
faults.04 ALARM R/O AlarmFlagRange R/O (Temp limit)
faults.05 ALARM R/O AlarmFlagRange R/O (Fan 1)
faults.06 ALARM R/O AlarmFlagRange R/O (Fan 2)
faults.07 ALARM R/O AlarmFlagRange R/O (Fan 3)
faults.08 ALARM R/O AlarmFlagRange R/O (Onboard sensor)
faults.09 ALARM R/O AlarmFlagRange R/O (Room sensor)
faults.10 ALARM R/O AlarmFlagRange R/O (Ambient sensor)
faults.11 ALARM R/O AlarmFlagRange R/O (Supply sensor)
faults.12 ALARM R/O AlarmFlagRange R/O (Condensor sensor)
faults.13 ALARM R/O AlarmFlagRange R/O (Digital 1)
faults.14 ALARM R/O AlarmFlagRange R/O (Digital 2)
faults.15 ALARM R/O AlarmFlagRange R/O (Door switch)
faults.16 ALARM R/O AlarmFlagRange R/O (Filter inout)
faults.17 ALARM R/O AlarmFlagRange R/O (Phase monitor)