This page describes the device driver and the device window for the Emerson / Liebert Air Conditioning System Model HPM with IntelliSlot Web Card.
Device window pages
The following table shows which device window pages are available with this individual device type.
--- The operational parametersConfiguration parameters
At the maintenance page of the device window there are a couple of configuration parameters which must be set to make the software talk to the unit.
Variables defined by this device driver
| name | type | flags | range |
|---|---|---|---|
| info.driver | TEXT | R/O | StringRange R/O |
| lowLevel.cmd | TEXT | StringRange | |
| lowLevel.reply | TEXT | R/O | StringRange R/O |
| faults.99 | ALARM | R/O | AlarmFlagRange R/O (Communication) |
| faults.commstat | TEXT | R/O | StringRange R/O |
| info.type | TEXT | R/O | StringRange R/O |
| info.port | TEXT | R/O | StringRange R/O |
| info.frame | TEXT | R/O | StringRange R/O |
| info.agentModel | TEXT | R/O | StringRange R/O |
| info.agentFirmware | TEXT | R/O | StringRange R/O |
| info.agentSerial | TEXT | R/O | StringRange R/O |
| info.deviceModel | TEXT | R/O | StringRange R/O |
| info.deviceName | TEXT | R/O | StringRange R/O |
| config.maintenanceMargin | INTEGER | SAVE SETUP | IntegerRange (0 .. 100) |
| operationState | CHOICE | R/O | EnumRange R/O (NORMAL STARTUP NORMAL+WARNING NORMAL+ALARM ABNORMAL) |
| systemState | CHOICE | R/O | EnumRange R/O (OFF ON STANDBY) |
| operationMode | CHOICE | R/O | EnumRange R/O (MANUAL AUTO) |
| meas.temp.supplyAir | FLOAT | R/O | DoubleRange R/O (0.0 .. 0.0) |
| meas.temp.returnAir | FLOAT | R/O | DoubleRange R/O (0.0 .. 0.0) |
| meas.humidity.returnAir | FLOAT | R/O | DoubleRange R/O (0.0 .. 0.0) |
| state.humidifying | CHOICE | R/O | EnumRange R/O (OFF ON) |
| meas.humidifying | INTEGER | R/O | IntegerRange R/O (0 .. 0) |
| state.dehumidifying | CHOICE | R/O | EnumRange R/O (OFF ON) |
| meas.dehumidifying | INTEGER | R/O | IntegerRange R/O (0 .. 0) |
| state.fan | CHOICE | R/O | EnumRange R/O (OFF ON) |
| meas.fan | INTEGER | R/O | IntegerRange R/O (0 .. 0) |
| state.heating | CHOICE | R/O | EnumRange R/O (OFF ON) |
| meas.heating | INTEGER | R/O | IntegerRange R/O (0 .. 0) |
| state.freeCooling | CHOICE | R/O | EnumRange R/O (OFF ON) |
| meas.freeCooling | INTEGER | R/O | IntegerRange R/O (0 .. 0) |
| state.cooling | CHOICE | R/O | EnumRange R/O (OFF ON) |
| meas.cooling | INTEGER | R/O | IntegerRange R/O (0 .. 0) |
| maintenance.capacity | INTEGER | R/O | IntegerRange R/O (0 .. 0) |
| maintenance.year | TEXT | NOPRESET | StringRange |
| maintenance.month | TEXT | NOPRESET | StringRange |
| faults.01 | ALARM | R/O | AlarmFlagRange R/O (AC Summary) |
| faults.02 | ALARM | R/O | AlarmFlagRange R/O (Maintenance) |