1.406 NAIS-FP0

This page describes the device driver and the device window for the NAIS-FP0 device. This device controls the I/O ports of a Matsushita / NAiS FP0 PLC. It can handle the ports at the PLC base unit and at up to three extension moules. It communicates to the PLC through the programming port at the PLC base unit. (see the paragraph at the end of this chapter).

The NAIS-FP0 device driver is part of the sat-nms framework for M&C of plain digital I/O functions. Monitoring alarm circuits or controlling waveguide switches are indicatives for applications of this framework.

The application configuration normally does not access the NAIS-FP0 device driver directly. There are a couple of application level logical devices (e.g. Input , Output or WG-Switch ) which may use the NAIS-FP0 device driver as a low level driver to access the physical I/O ports.

Port addressing

The device driver gives access to the I/O ports through four integer variables each for inputs and for outputs. Each variable stands for up to 32 input or output ports. The variables are mapped to the PLC's internal I/O addresses following the NAiS addressing conventions:

The variables 'X0000' and 'Y0000' refer to the ports at the PLC base unit, 'X0020' and 'Y0020' to the ports at the first extenstion motule etc. Within the variables, the IO ports are addressed by bit positions. Example:

An input port which appears in the FP0 PLC as 'X0006' is accessed through the variable X0000 of the device driver. It is represented by the bit 2^6 in the variable (the least significant bit represents the 'X0000' input).

Device window pages

The following table shows which device window pages are available with this individual device type. Tool-bar functions not mentioned here are described at the general description of device windows .

Configuration parameters

At the maintenance page of the device window there are a couple of configuration parameters which must be set to make the software talk to the Fanuc PLC.

parameter description
address The packet address of the PLC device. Usually this is "01".
extModules Select the number of extension modules you have connected to the FP0. The driver ignores the changes to 'Y00x0' variables of unused modules and it does not read out / update the corresponding 'X00x0' variables.
Serial Remember to set the line parameters for the serial interface connected to the NAiS FP0 PLC. The setting required by the FP0 is 9600,O,8,1 .

Remarks

Variables defined by this device driver

name type flags range
info.driver TEXT R/O StringRange R/O
lowLevel.cmd TEXT StringRange
lowLevel.reply TEXT R/O StringRange R/O
faults.99 ALARM R/O AlarmFlagRange R/O (Communication)
faults.commstat TEXT R/O StringRange R/O
info.type TEXT R/O StringRange R/O
info.port TEXT R/O StringRange R/O
info.frame TEXT R/O StringRange R/O
internal.dummy HEX R/O HexRange R/O (0 .. 0)
config.extModules CHOICE SAVE SETUP EnumRange (0 1 2 3)
X0000 HEX R/O HexRange R/O (0 .. 0)
X0020 HEX R/O HexRange R/O (0 .. 0)
X0040 HEX R/O HexRange R/O (0 .. 0)
X0060 HEX R/O HexRange R/O (0 .. 0)
Y0000 HEX HexRange (0 .. 0)
Y0020 HEX HexRange (0 .. 0)
Y0040 HEX HexRange (0 .. 0)
Y0060 HEX HexRange (0 .. 0)
initialized TEXT R/O StringRange R/O