This page describes the device driver and the device window for the NAIS-FP-Inv-Alarm-Circuit device. This device monitors an alarm contact through an input port of a NAiS/Matsushita FPx programmable logic controller. The NAIS-FP-Inv-Alarm-Circuit device raises an alarm if the contact is closed, i.e. current flows through the PLC input:
| circuit | logical state | alarm state |
|---|---|---|
| OPEN | LOW | OK |
| CLOSED | HIGH | ALARM |
There also is a NAIS-FP-Alarm-Circuit device available, which provides an inverted sense.
Multiple devices of this type (and other members of the NAIS-FP-* -family) may refer to one single PLC device. To do so, configure these devices to share the serial interface of the PLC and set the configuration parameters of each particular switch/monitoring device to the same PLC (address) but to individual ports.
Device window pages
The following table shows which device window pages are available with this individual device type. Tool-bar functions not mentioned here are described at the general description of device windows .
--- This page is empty. It is contained for compatibility to other switch/monitoring devices of the NAIS-FP-* family.
--- The faults page.
--- The device info page.
--- The maintenance page. The configuration parameters described below are set at this page.Configuration parameters
At the maintenance page of the device window there are a couple of configuration parameters which must be set to make the software talk to the alarm monitoring input at the PLC.
| parameter | description |
|---|---|
| address | The packet address of the PLC device. Usually this is "01". |
| port | The address of the input port to be monitored. |
| Serial | Remember to set the line parameters for the serial interface connected to the FPx PLC device. It requires the somewhat unusual setting 9600,O,8,1 . With multiple NAIS-FP-* devices referring to the same PLC, the line speed needs to be setup only once. |
Remarks
Variables defined by this device driver
| name | type | flags | range |
|---|---|---|---|
| info.driver | TEXT | R/O | StringRange R/O |
| lowLevel.cmd | TEXT | StringRange | |
| lowLevel.reply | TEXT | R/O | StringRange R/O |
| faults.99 | ALARM | R/O | AlarmFlagRange R/O (Communication) |
| faults.commstat | TEXT | R/O | StringRange R/O |
| info.type | TEXT | R/O | StringRange R/O |
| info.port | TEXT | R/O | StringRange R/O |
| info.frame | TEXT | R/O | StringRange R/O |
| config.port | TEXT | SAVE SETUP | StringRange |
| faults.01 | ALARM | R/O | AlarmFlagRange R/O (Circuit) |