4.6.8 Modbus Output Setup Registers

Configuration of the IO-FEP2 outputs starts at register 03001. The setup data for each output covers 20 registers, meaning that the setup configuration for output 2 starts at 03021, for output 3 at 03041 and so on. Setup of output 32 starts at address 03621 and ends with and including 03637.

The register definitions for output 1 are:

  Register    Purpose               Remarks
  
  03001       output 1 type         0 = not used
              definition            1 = normal output
                                    2 = temperature control loop
                                        output
                                    3 = software controlled WG switch 
                                        muting output
                                    4 = hardware controlled WG switch 
                                        muting output
  03002       output 1 name         up to 29 characters + 
                                    0-termination in 15
                                    registers
  03017       output 1 invert       0 = not inverting, '1' in the 
                                        output register closes 
                                        circuit
                                    1 = inverting, '1' in the output
                                        register opens circuit
  

Remarks:

  1. Output type 2 (temperature control loop output) only can be set if temperature control loops are licensed. Without license, the output type will fall back to 0 (not used) when configured to this state.
  2. Output type 4 (hardware controlled WG switch muting output) cannot be set explicitly. This state is detected from the IO-FEP2 hardware, if the DIP switch for an output is set to (hardware controlled WG switch muting, this register becomes read-only and always reports 4