1.300 Hitec-HAFP-00-NAOS1

This page describes the monitoring only device driver and the device window for the Hitec antenna front panel including deicing parameters, temperatures and different summary alarms.
This driver version is customized for NAOS project. It is based on HAFP-00_EL_NAOS_AfpInterfaceControlDocument_V1.01 from 20220531. ACU parameters are not included as they are implemented directly in the Hitec-HACU-01-NAOS

The driver uses the Hitec protocol.
IP address and port should be given by the interface in the device setup.
Default communication port is 3000

Device window pages

The following table shows which device window pages are available with this individual device type.

Configuration parameters

At the maintenance page of the device window there are a couple of configuration parameters which must be set to make the software talk to the unit.

parameter description
address No address required
readBackDelay Defines the delay the driver uses when it reads back parameters recently commanded. The delay is initialized at a proved preset value which should not be changed under normal circumstances.

Variables defined by this device driver

name type flags range
info.driver TEXT R/O StringRange R/O
lowLevel.cmd TEXT StringRange
lowLevel.reply TEXT R/O StringRange R/O
faults.99 ALARM R/O AlarmFlagRange R/O (Communication)
faults.commstat TEXT R/O StringRange R/O
info.type TEXT R/O StringRange R/O
info.port TEXT R/O StringRange R/O
info.frame TEXT R/O StringRange R/O
config.readBackDelay INTEGER SAVE SETUP IntegerRange (100 .. 10000)
temp.outsite FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
temp.ahub FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
temp.driveCabinet FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
temp.powerCabinet FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
humidity.outsite FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
humidity.ahub FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
wind.speed FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
resetESLoop TEXT NOPRESET StringRange
bright.direction FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
bright.lux FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
pressure FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
rain.intensity FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
wind.direction FLOAT R/O DoubleRange R/O (0.0 .. 0.0)
deice.status CHOICE EnumRange (AUTO MANUAL)
deice.auto CHOICE EnumRange (OFF ON)
deice.requested BOOLEAN R/O BooleanRange R/O (true false)
deice.manualAC TEXT NOPRESET StringRange
deice.manualBD TEXT NOPRESET StringRange
deice.manualSub TEXT NOPRESET StringRange
deice.manualCycle TEXT NOPRESET StringRange
deice.heating BOOLEAN R/O BooleanRange R/O (true false)
deice.ac BOOLEAN R/O BooleanRange R/O (true false)
deice.bd BOOLEAN R/O BooleanRange R/O (true false)
deice.subref BOOLEAN R/O BooleanRange R/O (true false)
deice.cycle CHOICE R/O EnumRange R/O (AUTO MANUAL)
feedblower.status CHOICE R/O EnumRange R/O (OFF ON)
feedheater.status CHOICE R/O EnumRange R/O (OFF ON)
feedblower CHOICE EnumRange (OFF AUTO FORCED ON)
feedheater CHOICE EnumRange (OFF AUTO)
feedheater2 CHOICE R/O EnumRange R/O (OFF AUTO MANUAL ON)
state.rain BOOLEAN R/O BooleanRange R/O (true false)
climatic.status CHOICE EnumRange (ON OFF)
climatic.fan CHOICE R/O EnumRange R/O (OFF ON)
climatic.heater CHOICE R/O EnumRange R/O (OFF ON)
faults.01 ALARM R/O AlarmFlagRange R/O (Emergency stop)
faults.02 ALARM R/O AlarmFlagRange R/O (Drive summary)
faults.03 ALARM R/O AlarmFlagRange R/O (General summary)
faults.04 ALARM R/O AlarmFlagRange R/O (RF summary)
faults.05 ALARM R/O AlarmFlagRange R/O (Climatic summary)
faults.06 ALARM R/O AlarmFlagRange R/O (Deicing summary)
faults.07 ALARM R/O AlarmFlagRange R/O (Access summary)
faults.09 ALARM R/O AlarmFlagRange R/O (Final limit)
faults.10 ALARM R/O AlarmFlagRange R/O (Feed blower fuse)
faults.11 ALARM R/O AlarmFlagRange R/O (Feed blower)
faults.12 ALARM R/O AlarmFlagRange R/O (Deicing main fuse)
faults.14 ALARM R/O AlarmFlagRange R/O (Deicing surge protect)
faults.20 ALARM R/O AlarmFlagRange R/O (Deicing auto)
faults.21 ALARM R/O AlarmFlagRange R/O (Remote access)
faults.13 ALARM R/O AlarmFlagRange R/O (Feed heater)
faults.15 ALARM R/O AlarmFlagRange R/O (RF inhibit (fast))
faults.24 ALARM R/O AlarmFlagRange R/O (Dehyd low pressure)
faults.25 ALARM R/O AlarmFlagRange R/O (Hub Temp/Humidity)
faults.31 ALARM R/O AlarmFlagRange R/O (High power load 1)
faults.32 ALARM R/O AlarmFlagRange R/O (High power load 2)
faults.33 ALARM R/O AlarmFlagRange R/O (High power load 3)
internal.r INTEGER R/O IntegerRange R/O (0 .. 0)
internal.test INTEGER R/O IntegerRange R/O (0 .. 0)